Permit: T05CM04144

Parcel: 13216600A


Addresses:

4004 S PARK AV 02

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
11/10/2005 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*WATER PIPING TYPE K
PRESSURE TEST ON WATER 100H OK
PRESSURE TEST ON AIR PROCESS PIPING 100# OK
NOTE: 1: LISTING NOT VISABLE ON HEAVY WALL BLK PIPE.
FIELD WRAPPED ENTRIRE LENGTH.
11/09/2005 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*TYPE K COPPER BELOW GRADE. VERIFIED AS TYPE R. OK
ABOVE GRADE COPPER REQUIRED TO BE TYPE K PER PLAN SPECS.
1" C W TO BE SLEEVED WITH 4" ABS PER PLAN
SHOW LISTING FOR 1" SCH 80 BLK PIPE FOR C.A
C.A PIPING ALSO REQUIRED TO BE SLEEVED W/4" ABS PER PLAN