Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T05CM04144
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/10/2005 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :*WATER PIPING TYPE K PRESSURE TEST ON WATER 100H OK PRESSURE TEST ON AIR PROCESS PIPING 100# OK NOTE: 1: LISTING NOT VISABLE ON HEAVY WALL BLK PIPE. FIELD WRAPPED ENTRIRE LENGTH. |
|
11/09/2005 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999*TYPE K COPPER BELOW GRADE. VERIFIED AS TYPE R. OK ABOVE GRADE COPPER REQUIRED TO BE TYPE K PER PLAN SPECS. 1" C W TO BE SLEEVED WITH 4" ABS PER PLAN SHOW LISTING FOR 1" SCH 80 BLK PIPE FOR C.A C.A PIPING ALSO REQUIRED TO BE SLEEVED W/4" ABS PER PLAN |