Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/24/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 08/22/2005 | FRAMING | Partial Approval | IVRS - Inspection :* 1) 01045 - NEW WALL ON PLAN REQUIRES KICKERS PER DETAIL A/2.0 AND 2) EXISITING UTILITY ROOM WAS FRAMED SUCH THAT TOILET DOES NOT MEET ACESSIBILITY REQUIREMENTS. E.G. 18" REQUIRED ON PULL SIDE OF DOOR TO ADA RESTROOM. 3) PLEASE PROVIDE PAST PERMIT/PLAN THAT ALLOWED UTILITY ROOM FRAMING. |