Permit: T05CM04133

Parcel: 12403171B


Addresses:

1838 E 6TH ST


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T05CM04133

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
10/20/2005 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
10/14/2005 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*SECURE CLOSET FLANGES TO THE FLOOR
A BLAKE TEE IS LISTED TO BE USED IN A VERTICAL POSITION
ABOVE CEILING OK TO COVER.
10/10/2005 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :* NOT READY
I WANT TO SEE THE MOP SINK COMPLETED.
10/06/2005 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
09/29/2005 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :* OK TO COVER ALL AREAS
NEED TO SEE CLOSET FLANGES
09/23/2005 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
09/21/2005 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
09/20/2005 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) ALL VERTICAL PIPING TO HAVE MID STORY SUPPORT ALL OVERHEAD PIPING TO BE SUPPORTED AT EACH CHANGE OF DIRECTION OR ELEVATION AND AT THEN END OF BRANCHES, THE NO MORE THAN FOUR FEET BETWEEN HANGERS
09/06/2005 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) REVISED APPROVED PLAN ON SITE
2) PVC DWV UNDERGROUND OK TO COVER
3) WOULD LIKE TO SEE MANUFACTURER INSTALLATION MANUAL SHOWING FLOW CONTROL INSTALLATION
4) OK TO COVER ALL AREAS
09/02/2005 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) NO REVISED PLAN ON SITE-RED LINES WON'T SUFFICE
2) MAKE SURE THE ACCURATE REVISED APPROVED PLAN IS ON SITE, OR HAVE CLEAR RED LINES
3) OK TO COVER UNDERGROUND EXCEPT FOR WATER CLOSETS AND ONE FLOOR SINK VENT
4) FLOW CONTROL NOT IN READILY ACCESSIBLE AND VISIBLE LOCATION TO BE REMOVED