Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/01/2005 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 11/28/2005 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GABLE END TRUSSES NOT CLIPPED PER 1/SD3 2) NAIL PROTECT PLUMBING WITHIN 1 1/4" OF PLATE SURFACES 3) P-1 SHEAR NOT NAILED 4) TEMPORARY BRACING MUST BE NAILED WITH 2 NAILS EACH END AND ONE PER STUD 5) PORCH ROOF NOT NAILED SOUTH END 6) ROOF SHEATHING MUST BE INSTALLED WITH GRAIN ACCROSS TRUSSES 7) MANY ROOF PANELS NOT NAILED 8) ROOF SHEATHING MUST SPAN 3 TRUSSES |