Permit: T05CM04125

Parcel: 140377870

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
01/20/2006 FRAMING Approved IVRS - Inspection :*
01/17/2006 FRAMING Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspection
Truss above kitchen mech vent damaged-requires engineering. Do not cover
Seal floor penetration at kitchen
No second floor dwv water test
You have 3 failures for same item. Refee imposed, you have 5 days to pay refee
01/13/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) OVER BORED F5A TRUSS ABOVE KITCHEN VENT
2) NO DWV WATER TEST ABOVE 5 FEET ABOVE SECOND FLOOR
3) RED HEAD ANCHOR BOLTS LOOSE
01/12/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) OK TO INSULATE ONLY
12/15/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 8 STUDS AND ONE POST OVER BORED-ADD STUDS OR STUD SHOES
2) W/H VENT ABOVE CEILING INSTALLED BACKWARDS
3) OVER BORED F5A TRUSS
4) THA 418 HANGERS BENT NOT SUPPORTING HEADERS
5) WATER HEATER B-VENT REQUIRES 1" TO COMBUSTIBLE MATERIAL
6) NO DWV WATER TEST SECOND FLOOR
7) FIRESTOP N.W. 2ND FLOOR
8) SECURE WIRES WITHIN 8" OF BOX MASTER BR
9) ANCHOR BOLTS NOT PER NOTE C TWO WALLS