Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/20/2006 | FRAMING | Approved | IVRS - Inspection :* | |
| 01/17/2006 | FRAMING | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspection Truss above kitchen mech vent damaged-requires engineering. Do not cover Seal floor penetration at kitchen No second floor dwv water test You have 3 failures for same item. Refee imposed, you have 5 days to pay refee |
|
| 01/13/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) OVER BORED F5A TRUSS ABOVE KITCHEN VENT 2) NO DWV WATER TEST ABOVE 5 FEET ABOVE SECOND FLOOR 3) RED HEAD ANCHOR BOLTS LOOSE |
|
| 01/12/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) OK TO INSULATE ONLY |
|
| 12/15/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 8 STUDS AND ONE POST OVER BORED-ADD STUDS OR STUD SHOES 2) W/H VENT ABOVE CEILING INSTALLED BACKWARDS 3) OVER BORED F5A TRUSS 4) THA 418 HANGERS BENT NOT SUPPORTING HEADERS 5) WATER HEATER B-VENT REQUIRES 1" TO COMBUSTIBLE MATERIAL 6) NO DWV WATER TEST SECOND FLOOR 7) FIRESTOP N.W. 2ND FLOOR 8) SECURE WIRES WITHIN 8" OF BOX MASTER BR 9) ANCHOR BOLTS NOT PER NOTE C TWO WALLS |