Permit: T05CM04114

Parcel: 11005320B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/10/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/09/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20
IDENTIFY UNGROUNDED CONDUCTORS PER 200. 7
PANEL LABELS TO BE ON OUTSIDE OF COVER
11/08/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING 314.20
MISSING PANEL COVER AND CIRCUIT DIRECTORY
FINISH FLOOR BOXES
NEED REJECTION PINS AT MAIN DISCONNECT
LABEL DISCONNECT-PANELS ON COVER