Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05CM04107
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/29/2005 | ELECTRIC - FINAL | Approved | SUBJECT TO LAST INSPECTION. IVRS - Inspection :* | |
09/12/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ROOF-SUPPORT GUTTER, SEAL HOLES IN DISCONNECT, PROPERLY FUSE UNIT, RUNG GROUND IN FLEX, SUPPORT FLEX OF ROOF 2) FRONT O/S FIXTURES TO BE DAMP LOCATION APPROVED 3) CLOSE OFF OPEN BOXES SHOWING WIRING 4) SERVICES OK |
|
09/09/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) BOND NEUTRAL IN SERVICE DISCONNECTS 2) BOND BUSHING REQUIRED ON NIPPLES FOR UNPROTECTED SIDE OF SERVICE CONDUCTORS 3) INSTALL REJECTION PINS |