Permit: T05CM04097

Parcel: 12710017D


Addresses:

899 N WILMOT RD #C2


Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Permit Number - T05CM04097

Inspection Description - ELECTRIC - FINAL

Inspection Status - Partial Approval

Date Description Inspector Results Comments
06/21/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
SERVICE
1. CANNOT TRIM CONDUCTOR - USE ALL STRANDS SES
2. MAINTAIN WORKING CLEARANCES SES 110.26
3. WHERE IS CONDUIT STRAP MAIN
12/29/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
1) PLEASE PROVIDE ACCESS AND HAVE ELECTRICIAN PRESENT
10/04/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. MAINTAIN WORKING SPACE IN FRONT OF AC DISCONNECTS
2. TIGHTEN LOOSE FITTINGS
3. MISSING JUNCTION BOX COVER
4. SEE WRITE UP FOR BUILDING "E"