Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
Permit Number - T05CM04097
Inspection Description - ELECTRIC - FINAL
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/21/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* SERVICE 1. CANNOT TRIM CONDUCTOR - USE ALL STRANDS SES 2. MAINTAIN WORKING CLEARANCES SES 110.26 3. WHERE IS CONDUIT STRAP MAIN |
|
12/29/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* 1) PLEASE PROVIDE ACCESS AND HAVE ELECTRICIAN PRESENT |
|
10/04/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. MAINTAIN WORKING SPACE IN FRONT OF AC DISCONNECTS 2. TIGHTEN LOOSE FITTINGS 3. MISSING JUNCTION BOX COVER 4. SEE WRITE UP FOR BUILDING "E" |