Permit: T05CM04090

Parcel: 140182500

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T05CM04090

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/29/2006 BUILDING - FINAL Approved IVRS - Inspection :*
06/26/2006 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CONDENSATE DISCONNECT LACKS REQUIRED 36" CLEARANCE/SECURE LIQUID TIGHT
2) PROVIEE 4" CLEARANCE FROM STUCCO WEEP SCREED GRADE AWAY FROM HOUSE
3) MISSING LIGHT FIXTURE NORTH ENTRANCE DOOR
4) BEDROOM CLOSET AND LAUNDRY FIXTURES WITHIN 12" STACKABLE COMBUSTIBLES FROM SHELVING
5) WATER HEATER LOCATION NOT PER PLAN
6) CLEAR DEBRIS AIR HANDLER PAN IN ATTIC
05/19/2006 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
1) CANCELLED PER SUPER