Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/28/2006 | FRAMING | Approved | IVRS - Inspection :* | |
| 12/06/2005 | FRAMING | Partial Approval | IVRS - Inspection :* 1) PENDING MECH 2) APPROVED TO INSULATE 3) RELOCATE FRESH AIR INTAKE |
|
| 12/05/2005 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED |
|
| 12/01/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) EXTENSION RING REQUIRED ON LIGHT OUTLET AT BACK PATIO 2) CONNECT EXHAUST FAN DUCT AT POWDER 3) SEPERATE BUNDLED HOME RUNS 4) BANG PLATE N. GARAGE WALL 5) FIRESTOP 2ND FLOOR PENETRATION 6) FIRESTOP 3" ABS CHASE AT POWDER 7) ABS OUT OF WALL IN MASTER BATH 8) PROTECT 220 FROM H2.5 OVER MASTER BATH 9) PROTECT ROMEX FROM TRUSS MASTER BED, L.R. 10) TAPE HVAC DUCT OVER L.R. 11) FRESH AIR INTAKE REQUIRES 10' MINIMUM CLEARANCE TO EXHAUST 12) SUPPORT VTR OVER 2ND FLOOR BAHT (X2) 13) NO DWV 2ND FLOOR 14) NO TEST ON POTABLE WATER 15) STOPPED INSPECTION |