Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
02/28/2006 FRAMING Approved IVRS - Inspection :*
12/06/2005 FRAMING Partial Approval IVRS - Inspection :*
1) PENDING MECH
2) APPROVED TO INSULATE
3) RELOCATE FRESH AIR INTAKE
12/05/2005 FRAMING Not ready for Inspection IVRS - Inspection :*
1) CANCELLED
12/01/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) EXTENSION RING REQUIRED ON LIGHT OUTLET AT BACK PATIO
2) CONNECT EXHAUST FAN DUCT AT POWDER
3) SEPERATE BUNDLED HOME RUNS
4) BANG PLATE N. GARAGE WALL
5) FIRESTOP 2ND FLOOR PENETRATION
6) FIRESTOP 3" ABS CHASE AT POWDER
7) ABS OUT OF WALL IN MASTER BATH
8) PROTECT 220 FROM H2.5 OVER MASTER BATH
9) PROTECT ROMEX FROM TRUSS MASTER BED, L.R.
10) TAPE HVAC DUCT OVER L.R.
11) FRESH AIR INTAKE REQUIRES 10' MINIMUM CLEARANCE TO EXHAUST
12) SUPPORT VTR OVER 2ND FLOOR BAHT (X2)
13) NO DWV 2ND FLOOR
14) NO TEST ON POTABLE WATER
15) STOPPED INSPECTION