Permit: T05CM04081

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
10/18/2005 EXT METAL CLIPS/EXT SHEATHING Approved
10/16/2005 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) LOOSE ROOF SHEATHING AT FRONT OF GARAGE
2) DBL STUDS REQUIRED UNDER GIRDERS IN LIVING ROOM
3) RETRO H.D.'S WHERE MISSING
4) RAT RUN BRACING PER TRUSS ENGINEER
5) NAILS MISSING IN EAST SIDE SHEATHING AT 2ND FLOOR LEVEL
10/13/2005 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) NOT COMPLETE ENOUGH TO INSPECT