Inspection Status: Approved
Inspection History: PLUMBING - PROGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/19/2006 | PLUMBING - PROGRESS | Approved | IVRS - Inspection :* | |
| 01/11/2006 | PLUMBING - PROGRESS | Partial Approval | IVRS - Inspection :* 1) RAIN LEADER AT SOUTH EAST CORNER IS OK TO COVER. #14 AND 19 |
|
| 01/09/2006 | PLUMBING - PROGRESS | Partial Approval | IVRS - Inspection :* 1) ROOF DRAIN AT S.E. CORNER DENIED 2) PIPING SUPPORT CANNOT BE ON COUPLING (ABS) 3) USE PROPER COUPLING MISSION COUPLING USED IS FOR C1 TO PL. IF MISSION COUPLING IS TO BE USED, USE ONE DESIGNED FOR PL TO PL 4) YARD WATER LINE AT RP LOCATION, SCHEDULE 40 PVC OK TO COVER 5) PROVIDE TUCSON WATER PERMIT FOR NEW RP 6) PROVIDE CERTIFICATION PAPERWORK FOR RP |
|
| 01/03/2006 | PLUMBING - PROGRESS | Denied | IVRS - Inspection : See detailed listing on site.| 999* 5" NH BAND DRIPPING |
|
| 12/30/2005 | PLUMBING - PROGRESS | Partial Approval | IVRS - Inspection :*R.W.L WATER TEST IS OK NOTE: 5' EXISTING CAST IRON R W L @ SOUTH EAST CORNER OF BLDG. IS LEAKING |
|
| 12/22/2005 | PLUMBING - PROGRESS | Partial Approval | IVRS - Inspection :* |