Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T05CM04064
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/04/2006 | FRAMING | Approved | IVRS - Inspection :* | |
11/02/2006 | FRAMING | Partial Approval | IVRS - Inspection :* 1) 9" ON CENTER HILTI PINS GARAGE TO HOUSE 2) PLUMBING AND FRAMING NOT SIGNED OFF |
|
11/01/2006 | FRAMING | Partial Approval | IVRS - Inspection :* 1) NO DWV TEST 2) 2003 IRC R807.1 THE ROUGH FRAME OPENING SHALL BE NOT LESS THAT 22" BY 30 " 3) ACCESS IS STILL OBSTRUCTED BY DRIP PAN |
|
10/31/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) TIGHTEN RED HEADS 2) EXTEND A/C LINE TO OUTSIDE OF BLDG 3) NO DWV TEST 4) NO TEST ON SOLAR WATER LOOP PIPES 5) OVER FLOW PAN INCROACHES ON AA |
|
09/15/2006 | FRAMING | Not ready for Inspection | IVRS - Inspection :* |