Permit: T05CM04063

Parcel: 141017020

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T05CM04063

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
12/19/2006 FRAMING Approved IVRS - Inspection :*
11/02/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FROM LAST INSPECTION SECURE REAR RETRO/HD
2) GARAGE TO HOUSE SHEAR NAIL BOTTOM PLATE 9" ON CENTER HILTI PINS ALSO PLATE JOINT WEST WALL GARAGE
3) NO HANDLE ON BIB FOR UFER GROUND
4) ADD CRIPPLES OVER WINDOW, DINING ROOM WEST
5) NO HANDLE ON BIB FOR DWV TEST
6) OVERFLOW PAN NOT SUPPORTED ATTIC, DUCT NOT CONNECTED TO FURNACE
7) GAS/POTABLE H20 OK
10/31/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NAIL OFF RETRO H/D
2) LEAVE RESULTS OF PRIOR INSPECTIONS ON SITE
3) NO SUPPLY OR DWV TEST
4) SUPPLY LINES STAPLED MASTER BATH
5) NEED 12" CLEAR PEX TO CAN LIGTH MASTER
6) STOPPED INSPECTION
10/30/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) STUCCO MESH NOT COMPLETE
2) NO PLANS OR PAPERWORK
3) STOPPED INSPECTION