Permit: T05CM04059

Parcel: 134160200


Addresses:

931 S MARVIN AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/26/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/31/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
RELOCATE CONDENSATE TO DRIP ONTO DIRT.
CANNOT RUN EXPOSED PIPE ACCROSS A SIDEWALK
VENT ON CONDENSATE TRAP MUST BE DOWNSTREAM OF TRAP
PROVIDE A MIN 10 LB. TEST ON GAS PIPE
GAS FLEX CONNECTOR CANNOT EXCEED 3' IN LENGTH.
PROVIDE ROOF JACKS AT ROOF PENETRATIONS
08/12/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE MINIMUM 10 POUND PRESSURE TEST ON ALL NEW GAS PIPING
2) REMOVE UNION FROM GAS LINE IN CLOSET
3) USE REVERSE THREAD COUPLING AND NIPPLE IF NECESSARY
4) DO NOT USE AN EMT COUPLING TO CONNECT TO PANEL
5) IDENTIFY CIRCUIT BREAKER
6) CANNOT TERMINATE CONDENSATE INTO A SEWER VENT
7) TERMINATE DOWN TO DIRT
8) PAINT PVC WITH LATEX PAINT
9) BLOCK AND CLAMP EVERY 4". SLOPE MINIMUM 48" PER FT.
10) 3/8" ID GAS FLEX NOT ADEQUATE FOR 120,000 BTU
11) RECALL FOR INSPECTION