Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/26/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/31/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* RELOCATE CONDENSATE TO DRIP ONTO DIRT. CANNOT RUN EXPOSED PIPE ACCROSS A SIDEWALK VENT ON CONDENSATE TRAP MUST BE DOWNSTREAM OF TRAP PROVIDE A MIN 10 LB. TEST ON GAS PIPE GAS FLEX CONNECTOR CANNOT EXCEED 3' IN LENGTH. PROVIDE ROOF JACKS AT ROOF PENETRATIONS |
|
| 08/12/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE MINIMUM 10 POUND PRESSURE TEST ON ALL NEW GAS PIPING 2) REMOVE UNION FROM GAS LINE IN CLOSET 3) USE REVERSE THREAD COUPLING AND NIPPLE IF NECESSARY 4) DO NOT USE AN EMT COUPLING TO CONNECT TO PANEL 5) IDENTIFY CIRCUIT BREAKER 6) CANNOT TERMINATE CONDENSATE INTO A SEWER VENT 7) TERMINATE DOWN TO DIRT 8) PAINT PVC WITH LATEX PAINT 9) BLOCK AND CLAMP EVERY 4". SLOPE MINIMUM 48" PER FT. 10) 3/8" ID GAS FLEX NOT ADEQUATE FOR 120,000 BTU 11) RECALL FOR INSPECTION |