Permit: T05CM04058

Parcel: 12710017D

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T05CM04058

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/17/2005 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) OK FOR FINAL C OF O
08/08/2005 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SECONDARY CONDENSATE DRAIN MUST TERMINATE IN A CONSPICUOUS LOCATION, NOT AT SAME LOCATION AS PRIMARY
2) PAINT PVC WITH LATEX PAINT
3) SECURE REFER LINES TO WALL OUTSIDE
4) TAPE IS FALLING OFF REFER LINE JOINTS
5) SEAL THE HOLE IN THE WALL AROUND REFER LINES AND DRAIN LINES
6) A CONSPICUOUS LOCATION SHOULD ALTERT THE TENANT THAT THERE IS A PROBLEM WITH PRIMARY DRAIN. YOU CAN DRIP OUTSIDE OVER A WINDOW. DO NOT RUN PIPE TO THE GROUND