Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T05CM04023
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/31/2005 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 09/23/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PLEASE PROVIDE A LETTER AUTHORIZING USAGE OF M/C & A/C CABLES. 2. HOME RUNS FOR PATIENT CARE AREAS TO BE AS PER 517.13. 3. MAINTAIN FIRE WALL SEPARATION. OK WALLS SUBJECT TO LETTER. | |
| 09/22/2005 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) FINISH WORK |
|
| 09/20/2005 | ELECTRIC - INTERMEDIATE | Cancelled | IVRS - RI canceled | |
| 09/18/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK 2 PVC CONDUITS UNDER SLAB 1) PROTECT CONDUITS AT BASE PLATE |