Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T05CM04022
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/24/2005 | MECHANICAL - ABOVE CEILING | Approved | ||
08/22/2005 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) SEAL OPENINGS IN OUTSIDE WALLS OF PLENIUM |
|
08/15/2005 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) OPEN CEILING TO EXPOSE ALL FAN COILS 2) REVISE PLANS TO SHOW ALL NEW FAN COILS INSTALLED 3) STRAP FLEX DUCT UP OFF OF LIGHTS AND GRID 4) REMOVE PLASTIC CAPS FROM DRAIN OUTLETS 5) PIPE SECONDARY DRAINS TO A CONSPICOUS LOCATION |