Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T05CM04022
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/08/2005 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
09/01/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK TEMP C OF O SUBJECT TO OTHER INSPECTIONS 2) WAITING ON REVISED PLANS |
|
08/25/2005 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) FINISH VDV CABELING AS DISCUSSED 2) BOXES MORE THAN 1/4" FROM BOX TO SURFACE TO USE APPROVED EXTENDER RINGS 314.20 3) PLANS AND PANEL DO NOT MATCH-PLEASE REVISE OR INSTALLA AS PER PLANS 4) IDENTIFY CONDUCTOR COLORES FOR ALL CONDUCTORS 5) SEPERATE GROUNDS AND NEUTRALS 250.24 6) PLEASE VERIFY DERATING OF CONDUCTORS PER 310.15 7) PROVIDE A BOND BUSING ACCROSS CUT CONCENTRICS AND KNOCKOUTS 8) REVISE PANEL SCHEDULES 9) LABEL PANELS ON OUTSIDE COVER 10) SUPPRT CONDUITS WITHIN 3' OF PANEL |
|
08/19/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) VDV CABELING TO BE AS PER 725.6 2) EXPOSED CONDUCTORS ABOVE CEILING 3) OK LIGHTING 4) OK WALLS SUBJECT TO PLAN REVISED AND STAMPED |
|
08/08/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) PROTECT CABLE AT TOP PLATES 2) OK NEW FRAME WALLS |