Permit: T05CM04021

Parcel: 141153540

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05CM04021

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/30/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/28/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) YOU STILL HAVE OVER 10 CURRENT CARRYING CONDUCTORS INSTALLED IN THE SAME CONDUIT THE ADJUSTMENT IS 50 PERCENT CAPACITY (TABLE 310.15 (B) (2) (A) TABLE 310.16 LIST #12 THWN AT THE 75 DEGREE COLUMN (WHICH IS WHAT THIS PANEL IS RATED AT) AT 25 AMPS SO PER TABLE 310.15 B2A THE CONDUCTOR MUST BE PROTECTED AT 12.5 AMPS MAX
11/22/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* PER TABLE 310.15 B2A ADJUSTMENT FACTOR NEEDS TO BE DERATED PER THESE TABLES
SECURE MC CABLE WITHIN 12" O? ALL J-BOXES ( CEILING)