Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/15/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
09/08/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PROPERTY INSTALL SEAL TITE WITH FITTINGS 2) DO ARRAYS MEET REQUIREMENTS OF 690.4(C) 3) FINISH #4 PREVIOUS INSPECTION |
|
09/01/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) USE LISTED AND APPROVED FITTINGS FOR SEAL TITE 2) GROUND CONDUCTOR SMALLER THAN PLANS 3) A BOND BUSHING IS NEEDED AT REDUCING WASHER 4) TIGHTEN ALL LOOSE FITTINGS ON ROOF 5) FLEX CONDUIT NOT LISTED FOR WET LOCATION 6) ONLY ON CONDUCTOR PER LUG TERMINATION 7) SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING 8) GROUND TERMINATIONS ON PV ? TO BE UNDER SCREW IN A CLOCK WISE DIRECTION |