Permit: T05CM04019

Parcel: 141015550

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05CM04019

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/15/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/08/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) PROPERTY INSTALL SEAL TITE WITH FITTINGS
2) DO ARRAYS MEET REQUIREMENTS OF 690.4(C)
3) FINISH #4 PREVIOUS INSPECTION
09/01/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) USE LISTED AND APPROVED FITTINGS FOR SEAL TITE
2) GROUND CONDUCTOR SMALLER THAN PLANS
3) A BOND BUSHING IS NEEDED AT REDUCING WASHER
4) TIGHTEN ALL LOOSE FITTINGS ON ROOF
5) FLEX CONDUIT NOT LISTED FOR WET LOCATION
6) ONLY ON CONDUCTOR PER LUG TERMINATION
7) SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING
8) GROUND TERMINATIONS ON PV ? TO BE UNDER SCREW IN A CLOCK WISE DIRECTION