Permit: T05CM03977

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
10/07/2005 FRAMING Approved IVRS - Inspection :*
10/06/2005 FRAMING Partial Approval IVRS - Inspection :*
1) ITEM 03050 NOT REQUIRED-NO GAS-ALL ELECTRIC
2) PARTIAL FOR HOLDOWNS NOT INSTALLED
10/05/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SEAL LATH PENETRATION EAST WALL
2) FHA STRAPS MISSING NAILS
3) FIREBLOCK PLUMBING CHASE AT KITCHEN
4) PLUMBERS TAPE NOT ALLOWED FOR ABS SUPPORT
5) OVER SPAN AT GARAGE SHEAR WALL
6) INSTALL FHA STRAPS DBL TOP PLATE MASTER CLOSET
7) F3 TRUSSES MISSING BLOCKS
8) SHIM HEADERS WHERE NEEDED
9) UNTREATED STAIR STRINGER IN CONTACT WITH CONCRETE
1) DWV'S HAVE NO WATER TO 2ND FLOOR
11) FIRE BLOCKS MISSING AT LAUNDRY
12) HANGER IN LAUNDRY MISSING NAIL
13) RIDGE BLOCK CRACKED
14) OVERSPAN UPSTAIRS MIDDLE BEDROOM NORHT WALL
15) ENSURE ALL BEDROOMS AND SMOKE DETECTORS ARC ON ARC FAULT CIRCUITS AND WATER HEATER HAS A DISCONNECT
16) STOPPED INSPECTION