Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05CM03968
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/13/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1. CHANGE WATER HEATER FUSES TO 25 OR 30 AMP. |
|
| 06/12/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. REMOVE BONDING JUMPER ALL THE WAY IN PANEL. 2. BOND EQUIPMENT GROUNDS TO ENCLOSURE IN PANEL 3. WATER HEATER BRANCH CKT TO BE MINIMUM 30 AMP 4. PROVIDE ROOF ACCESS 5. WILL HAVE REINSPECTION FEE IF NOT CORRECT NEXT TRIP. |
|
| 06/09/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. BRANCH CKT TO WATER HEATER IS UNDERSIZED NEC 422.10 (A) 2. EMERGENCY LIGHTING NOT WORKING. 3. MINIMUM SIZE EQUIPMENT GROUND FOR 30 AMP RTU'S IS #10 NEC 250.122 4. GROUND AND NEUTRALS MUST BE SEPARATED IN SUB-PANEL NEC 250.122 5. INSTALL EXTERIOR LIGHTS ON W.P COVERS 6. GROUND PANEL ENCLOSURE |