Permit: T05CM03937

Parcel: 12901044C


Addresses:

1940 E BROADWAY BL


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T05CM03937

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/09/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
OK FOR FINAL
12/13/2006 MECHANICAL - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio
WORK NOT READY 2 DAYS IN A ROW.
PAY A REINSPECTION FEE PRIOR TO NEXT INSPECTION.
12/13/2006 MECHANICAL - FINAL Partial Approval OKAY FOR TEMP C OF O PER COMMENTS ON 12/12/06 PER JMILITEL
12/12/2006 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
ACCESS DOORS PROGRESSING
OK TO FILE FOR TEMP C OF O
12/11/2006 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. CHECKED PAN WASHER VENT
2. FOLLOW INSTALL INSTRUCTIONS FOR CLEAN OUT ACCESS DOORS.
3. FASTENERS CANNOT PENETRATE THE GREASE DUCT.
12/08/2006 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE DOUBLE WALL VENT PIPE ON PAN WASHER
2. SECURE AS NEEDED.
3. PROVIDE CLEANOUTS IN TYPE 1 DUCTS
4. NEED TO TEST HOODS
5. RELOCATE CONTROL BOX BLOCKING DATA PLATES ON A/C UNITS.
6. CONDENSOR OVERFUSED
7. IDENTIFY CONDENSOR
8. PROVIDE SERVICE RECEPTACLE WITHIN 25' OF ALL EQUIPMENT ON ROOF.
12/06/2006 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. SMALL CARRIER CONDENSORS <ROOFTOP> OBLONG
CONFIGURATION LAG BOLT OPPOSITE CORNERS TO PLATFORM.
2. COMPLETE ELECTRICAL TO ALL ROOFTOP COMB. UNITS NOT INCLUDING LARGE MAIN UNIT.
3. COMPLETING WRAP ON SUPPLY TAPE ABOVE GRID,
BAKERY AREA -- COOKING AREA ABOVE TYPE I HOOD.
4. EXHAUST BLWRS. ON ROOF OK