Permit: T05CM03937

Parcel: 12901044C


Addresses:

1940 E BROADWAY BL


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T05CM03937

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
01/10/2007 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
12/05/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PROVIDE REVISED APPROVED PLANS FROM THE CITY.
2. COMPLETE ALL WORK BEFORE CALLING FOR FINAL.
10/24/2006 PLUMBING - INTERMEDIATE Partial Approval 1. 3" VENTS FOR CWV ALONG FROZEN FOOD AISLES THRU ROOF OK WITH EXCEPTION; ABS TO BE SUPPORTED AT EACH CHANGE OF DIRECTION OR ELEVATION AND AT THE END OF BRANCHES THEN NO MORE THAN FOUR FEET BETWEEN HANGERS. OK FOR CASES
10/17/2006 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
TEST ON ROOF DRAINS IN FRONT OF STORE
REDLINE DRAWINGS TEST OK
10/16/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. STARBUCKS VENT TEST OK AND VENT ON NORTH WALL EAST OF STARBUCKS OK.
2. STARBUCKS UNDERGROUND WATER TEST OK
10/12/2006 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. MEZZANINE ADD SUPPORT ON WATER & VENT PIPING
2. 10 MIL. TAPE ON COPPER METER STUDS.
10/09/2006 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
10/05/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
PARTIAL APPROVED FOR PRODUCE PREPARATION WATER PIPING.
09/29/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
WASTE & VENT EMPLOYEE RESTROOM & WATER PIPING SAME INSTALLED ON PLAN.
WASTE & VENT WATER TEST THRU ROOF RECEIVING (2) FLOOR SINKS OK.
1. TRAP PRIMERS SHALL BE INSTALLED FOR ALL TRAPS WHICH MAY ONLY RECEIVE FLOW FROM SEASONAL CONDITIONS.

VENTS THRU ROOF FLOORSINKS, WASTE & VENT SINKS THRU ROOF, MEAT AREA, PRODUCE AREA & COMBO WASTE & VENT PER INITIAL OK
09/28/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
90 PSI AIR TEST WATER PIPING FOR EMPLOYEE RESTROOM SOUTH CENTER WITH MOP SINK OK
SHALL TEST WASTE & VENT THRU ROOF & SUPPORT OVERHEAD CORRECTLY.
09/21/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. GAS PIPING ON SOUTH WALL AND SOUTHEAST WALL OK
2. WATER TEST NOT HOLDING ON SOUTH & SOUTHEAST WALL.

100 PSI SOUTH WATER
100 PSI CENTER WALL
60 PSI 3/4 GAS
10 PSI 1 1/2 GAS
SOUTH 20 PSI
EAST WALL
SOUTH WALL
10 PSI WATER
EAST WATER 50 PSI
09/15/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
WATER PIPING AND VENT PIPING IN WALL TEST OK IN DELI
AND MAIN FROM SOON SUPPLY TO DELI HOT & COLD DCW