Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T05CM03937
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/10/2007 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
12/05/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PROVIDE REVISED APPROVED PLANS FROM THE CITY. 2. COMPLETE ALL WORK BEFORE CALLING FOR FINAL. |
|
10/24/2006 | PLUMBING - INTERMEDIATE | Partial Approval | 1. 3" VENTS FOR CWV ALONG FROZEN FOOD AISLES THRU ROOF OK WITH EXCEPTION; ABS TO BE SUPPORTED AT EACH CHANGE OF DIRECTION OR ELEVATION AND AT THE END OF BRANCHES THEN NO MORE THAN FOUR FEET BETWEEN HANGERS. OK FOR CASES | |
10/17/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* TEST ON ROOF DRAINS IN FRONT OF STORE REDLINE DRAWINGS TEST OK |
|
10/16/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. STARBUCKS VENT TEST OK AND VENT ON NORTH WALL EAST OF STARBUCKS OK. 2. STARBUCKS UNDERGROUND WATER TEST OK |
|
10/12/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. MEZZANINE ADD SUPPORT ON WATER & VENT PIPING 2. 10 MIL. TAPE ON COPPER METER STUDS. |
|
10/09/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
10/05/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PARTIAL APPROVED FOR PRODUCE PREPARATION WATER PIPING. |
|
09/29/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* WASTE & VENT EMPLOYEE RESTROOM & WATER PIPING SAME INSTALLED ON PLAN. WASTE & VENT WATER TEST THRU ROOF RECEIVING (2) FLOOR SINKS OK. 1. TRAP PRIMERS SHALL BE INSTALLED FOR ALL TRAPS WHICH MAY ONLY RECEIVE FLOW FROM SEASONAL CONDITIONS. VENTS THRU ROOF FLOORSINKS, WASTE & VENT SINKS THRU ROOF, MEAT AREA, PRODUCE AREA & COMBO WASTE & VENT PER INITIAL OK |
|
09/28/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 90 PSI AIR TEST WATER PIPING FOR EMPLOYEE RESTROOM SOUTH CENTER WITH MOP SINK OK SHALL TEST WASTE & VENT THRU ROOF & SUPPORT OVERHEAD CORRECTLY. |
|
09/21/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. GAS PIPING ON SOUTH WALL AND SOUTHEAST WALL OK 2. WATER TEST NOT HOLDING ON SOUTH & SOUTHEAST WALL. 100 PSI SOUTH WATER 100 PSI CENTER WALL 60 PSI 3/4 GAS 10 PSI 1 1/2 GAS SOUTH 20 PSI EAST WALL SOUTH WALL 10 PSI WATER EAST WATER 50 PSI |
|
09/15/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* WATER PIPING AND VENT PIPING IN WALL TEST OK IN DELI AND MAIN FROM SOON SUPPLY TO DELI HOT & COLD DCW |