Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T05CM03937
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/10/2007 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
12/05/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* | |
10/13/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1. GREASE TRAP PIPING TEST OK 2. HCS TIE INS TEST OK 3. MEZZANINE PIPING IN WALL OK 4. HAND IN PHARMACY TEST OK |
|
10/02/2006 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* CALL FOR YARDWATER AND HAVE DRAWINGS REDLINED. |
|
09/25/2006 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* PRE-SLAB STARBUCKS AREA OK PENDING REVISED APPROVED PLAN FROM CITY -- COVER AT OWN RISK. |
|
09/22/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1. STARBUCKS NEEDS TO HAVE APPROVAL PLANS FOR CHANGES UNDERGROUND GROUND OK PER PLANS TATE ARE NOT APPROVED. 2. BAKERY WALL VENTS & WATER PIPING OK |
|
08/24/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 3" WATER MAIN SOUTH SIDE ON TEST 3' UP WALL AND 5' OUT FROM BUILDING TEST OK |
|
08/11/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* | |
08/10/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* | |
08/07/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1. EAST OF PRODUCE BOX MAIN OK 2. MEAT & SEAFOOD PUMP TO ICE CREAM FREEZER OR MAIN |
|
08/03/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* MEAT DEPT. |
|
08/02/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1. PARTIAL ON (FLORAL TO PRODUCE) UNDERGROUND AIR TEST OK DUE TO RAIN. 2. RESTROOMS #118 JAN. CLOSET #120 UNDERGROUND AIR TEST OK DUE TO RAIN 3. RECEIVING #116 UNDERGROUND AIR TEST |
|
08/01/2006 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* | |
07/29/2006 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | CHECK #8607 RAINOUT |
|
07/25/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* CONTINUATION OF 4" GREASE WASTE FROM 7/18/06 WEST TO SEAFOOD/MEAT INCLUDING FLOOR DRAIN (4) FD-4 TO INITIAL 7/24/06 WATER TEST (PARTIAL) REPAIR LEAK ON 3" TO SEAFOOD FS-4 APPROX. 15' FROM 4" FCO AT WEST END. |
|
07/24/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 4" SANITARY DRAINAGE FROM STUB UP AT MEZZANINE THRU STARBUCKS THRU RESTROOM AREA, DELI, TIE IN FOR DAIRY CASES COMBINATION WASTE & VENT, BAKERY WATER TEST TO EXTERIOR OF BUILDING, 2-WAY CLEANOUT OK 1. PLAN IS APPROVED IN ERROR HANDSINK IN STARBUCKS REQUIRES DIRECT DRAINAGE CONNECTION. 2. 4" STUB UP FOR CONTINUATION OF SANITARY AT SOUTHEAST CORNER FOR CONTINUATION OF SANITARY TO WEST BUILDING. 3. 3-COMP SINK IN STARBUCKS SHOULD REQUIRE WASH/RINSE TO GO DIRECT DRAINAGE; SANITIZE TO INDIRECT. |
|
07/21/2006 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* | |
07/19/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | INSTALL OF ? ON COMBINATION WASTE AND VENT SYSTEM TAIL PIECES FOR FLOOR SINK IN DAIRY CASE AREA WATER TEST OK | |
07/18/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* CONTINUATION OF 4" GREASE WASTE FROM 7/13/06 INSPECTION TURNS SOUTH THRU EXTERIOR APP. 40' WITH COMBO TO CONTINUE TO WEST. WATER TEST OK MY INITIAL ON P1.1 4" SANITARY STUB 15' INTO BUILDING AT SOUTHEAST CORNER TO 6" BUILDING SEWER 40' OUT OF BUILDING INCLUDING 4" COMBO UP FOR FLOOR SINK. WATER TEST OK. 4" COMBINATION WASTE & VENT FOR DAIRY CASES FROM MY INITIAL P1.1 BACK UPSTREAM THRU VENTS TO F.F WATER TEST PARTIAL. 1. SHALL INSTALL REDUCER AT P-TRAP FOR TAILPIECES TO FIXTURE WITH RETEST. 2. ALL SHADING TO BE GOOD MATERIAL 1/2" MINUS. |
|
07/13/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 4" GREASE WASTE FROM DELI THRU BAKERY TO JUST BEFORE FCO TO EXIST BUILDING MY INITIAL ON P1.1 IN TRAILER WATER TEST OK |
|
07/12/2006 | PLUMBING - ROUGH, SOIL | Cancelled | IVRS - RI canceled |