Permit: T05CM03937

Parcel: 12901044C


Addresses:

1940 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05CM03937

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/12/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/09/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. 4S COVER MISSING ON J-BOX AT CONTROL CABINET IN BACK PANEL.
2. LABEL MISSING FOR PANEL CL - ALSO, PLUG HOLE IN DEAD FRONT.
3. PANEL CF DOOR LOCKED
4. INSTALL LABELS FOR PANEL L2 & L1
PLUG HOLES IN DEAD FRONT
5. PANEL EM BLOCKED WITH INVENTORY - MAIN 36" CLEARANCE PER CODE
6. PLEASE HAVE CONTR. ON SITE NEXT INSP. CHECK OUT EM LIGHTING THROUGHOUT BEFORE NEXT INSP.
12/13/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
COMPLETE LTG., CLOSE UP PANELS, EXTERIOR
12/12/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. COMPLETE CONDUIT RUNS & SUPPORT ABOVE PANELS
"BA" "FM"
2. COMPLETE SECURITY LTG.
3. COMPLETE WIRING PANEL & COVER

OK TCO
12/11/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
NOTES: KITCHEN, DELI, AREA, BAKERY
1. SUPPORT FLEX & MC CABLE PER CODE, DO NOT USE CEILING WIRES INTENDED TO SUPPORT GRID CEILINGS.
2. RECEPTS FOR PERSONNEL TO BE GFI PROTECTED UNLESS FOR SPECIFIC KITCHEN EQUIP.
3. EQUIP. OR APPLIANCES OVER 300 VA MUST HAVE DISCONNECTING MEANS UNLESS PANEL IS IN SITE.
4. INSTALL SEISMIC WIRES TO EACH GRID MTD. CAN LIGHT
5. OPEN J-BOXES THROUGHOUT, UNTERMINATED WIRING.

LIQUOR DEPT
1. SUPPORT MC & FLEX PER CODE ABOVE CEILING
2. OK CAN LIGHTS FOR SEISMIC WIRES.

CUSTOMER SERVICE
1. SEE OTHER NOTES, INSTALL ALL LABELS FOR PANELS, EQUIP, SES
2. ROOF OK