Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05CM03937
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/12/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
01/09/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. 4S COVER MISSING ON J-BOX AT CONTROL CABINET IN BACK PANEL. 2. LABEL MISSING FOR PANEL CL - ALSO, PLUG HOLE IN DEAD FRONT. 3. PANEL CF DOOR LOCKED 4. INSTALL LABELS FOR PANEL L2 & L1 PLUG HOLES IN DEAD FRONT 5. PANEL EM BLOCKED WITH INVENTORY - MAIN 36" CLEARANCE PER CODE 6. PLEASE HAVE CONTR. ON SITE NEXT INSP. CHECK OUT EM LIGHTING THROUGHOUT BEFORE NEXT INSP. |
|
12/13/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* COMPLETE LTG., CLOSE UP PANELS, EXTERIOR |
|
12/12/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. COMPLETE CONDUIT RUNS & SUPPORT ABOVE PANELS "BA" "FM" 2. COMPLETE SECURITY LTG. 3. COMPLETE WIRING PANEL & COVER OK TCO |
|
12/11/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* NOTES: KITCHEN, DELI, AREA, BAKERY 1. SUPPORT FLEX & MC CABLE PER CODE, DO NOT USE CEILING WIRES INTENDED TO SUPPORT GRID CEILINGS. 2. RECEPTS FOR PERSONNEL TO BE GFI PROTECTED UNLESS FOR SPECIFIC KITCHEN EQUIP. 3. EQUIP. OR APPLIANCES OVER 300 VA MUST HAVE DISCONNECTING MEANS UNLESS PANEL IS IN SITE. 4. INSTALL SEISMIC WIRES TO EACH GRID MTD. CAN LIGHT 5. OPEN J-BOXES THROUGHOUT, UNTERMINATED WIRING. LIQUOR DEPT 1. SUPPORT MC & FLEX PER CODE ABOVE CEILING 2. OK CAN LIGHTS FOR SEISMIC WIRES. CUSTOMER SERVICE 1. SEE OTHER NOTES, INSTALL ALL LABELS FOR PANELS, EQUIP, SES 2. ROOF OK |