Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/04/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
APPROVED LEE HANLY HOLDING FINAL ON PERMIT DUE TO OTHER WORK BEING DONE OR THAT HAS BEEN DONE PREVIOUSLY.
05/02/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
ELECTRIC FOR 400A
UPGRADE AND AC OK

INTERIOR WORK WITHOUT PERMITS MUST BE ADDRESSED
09/23/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*ALL OK PLEASE PROVIDE ACCESS TO ROOF, NEED TO CHECK WATER & GAS BOND
09/20/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) WE HAVE MULTIPLE TERMINATIONS AT GROUND IN METER SOCKET
2) BONDING JUMPERS TO BE SIZED PER 250.102 AND 250.66
3) DISCONNECT TO BE FUSED AND LABELED
4) CONDUCTOR IN RISER NOT AS PER PLANS
5) PLEASE VERIFY WATER AND GAS BONDS
6) SERVICE NOT AS PER PLANS
7) PLEASE VERIFY L-11 ELECTRICAL CONTRACTOR