Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/04/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* APPROVED LEE HANLY HOLDING FINAL ON PERMIT DUE TO OTHER WORK BEING DONE OR THAT HAS BEEN DONE PREVIOUSLY. |
|
| 05/02/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* ELECTRIC FOR 400A UPGRADE AND AC OK INTERIOR WORK WITHOUT PERMITS MUST BE ADDRESSED |
|
| 09/23/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*ALL OK PLEASE PROVIDE ACCESS TO ROOF, NEED TO CHECK WATER & GAS BOND | |
| 09/20/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WE HAVE MULTIPLE TERMINATIONS AT GROUND IN METER SOCKET 2) BONDING JUMPERS TO BE SIZED PER 250.102 AND 250.66 3) DISCONNECT TO BE FUSED AND LABELED 4) CONDUCTOR IN RISER NOT AS PER PLANS 5) PLEASE VERIFY WATER AND GAS BONDS 6) SERVICE NOT AS PER PLANS 7) PLEASE VERIFY L-11 ELECTRICAL CONTRACTOR |