Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/09/2005 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 09/08/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) PLUG UNUSED OPENINGS IN BOXES 2) SUPPORT MC WITHIN 12" AT TERMINATIONS AND AT 6' INTERVALS PER NEC 3) SEE NOTES PREVIOUS INSPECTIONS |
|
| 08/31/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LINE SIDE OF DISCONNECT IS NOT CONNECTED TO METER |
|
| 08/29/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) THE BUSHING AT BOTTOM OF DISCONNECT COMING FROM THE METER HAS TO BE A GROUNDING TYPE BECAUSE OF UNPROTECTED CONDUCTORS 250.92B NEC 2) CAN ELECTRICIAN VERIFY SET SCREW COUPLINGS USED OUTSIDE ARE WEATHER PROOF ON PANEL FEEDER |