Permit: T05CM03933

Parcel: 12504083C


Addresses:

1060 N CAMPBELL AV

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
09/09/2005 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
09/08/2005 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) PLUG UNUSED OPENINGS IN BOXES
2) SUPPORT MC WITHIN 12" AT TERMINATIONS AND AT 6' INTERVALS PER NEC
3) SEE NOTES PREVIOUS INSPECTIONS
08/31/2005 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) LINE SIDE OF DISCONNECT IS NOT CONNECTED TO METER
08/29/2005 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) THE BUSHING AT BOTTOM OF DISCONNECT COMING FROM THE METER HAS TO BE A GROUNDING TYPE BECAUSE OF UNPROTECTED CONDUCTORS 250.92B NEC
2) CAN ELECTRICIAN VERIFY SET SCREW COUPLINGS USED OUTSIDE ARE WEATHER PROOF ON PANEL FEEDER