Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/12/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* APPROVED PER APPROVED PLANS |
|
| 07/10/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE TEST ON ALL PIPING. 2. PROVIDE APPROVED COUPLING AT VENT CONNECTION TO EXISTING. 3. NOTE: PUBLIC USE LAVS REQUIRES THAT WATER HEATER NOT BE SOLE CONTROL OF HOT WATER TEMPERATURE NOT TO EXCEED 110 DEGREES. TEMPERING SHALL BE REQUIRED. 4. INSTALL WATER PIPING PER PLAN FROM METER THRU NEW RPA TO BUILDING. 5. PROVIDE VACUUM BREAKERS AT ALL HOSE BIBBS. 6. WATER HEATER SHALL REQUIRE PAN & PAN DRAIN T&P AND PAN DRAIN SHALL GRAVITY DRAIN TO DAYLIGHT. |