Permit: T05CM03908

Parcel: 13219015B


Addresses:

2200 E BENSON HY


Inspection Status: Approved

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Permit Number - T05CM03908

Inspection Description - EXCAVATION/LAYOUT REBAR & ZON

Inspection Status - Approved

Date Description Inspector Results Comments
01/13/2006 EXCAVATION/LAYOUT REBAR & ZON Approved IVRS - Inspection :*
01/11/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
1. FOOTINGS INSTALLED PER BUNGER STEEL SHOP DRAWINGS
2. YOU MUST GET REVISED PLAN - POURING CONCRETE WILL BE AT YOUR OWN RISK
01/10/2006 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FOOTING LAYOUT DOES NOT MATCH PLAN
01/09/2006 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CUT THROUGH NORTH FOOTINGS IS GIVEN AS 1/S4 THERE IS NO PAGE 54
2) IF ENGINEER MEAN 1/53 THEN YOU ARE LACKING VERTICAL STEEL PER PLAN. ALSO VERIFY IF 2 NORTH CORNER FOOTINGS ARE TYPE F-1 OR IF THEY ARE CONCRETE PEDESTAL
3) YOU HAVE 2 EXTRA FOOTINGS NOT SHOWN ON PLAN, WHY?