Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T05CM03900
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/20/2006 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
| 06/14/2006 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) UNCOVER ALL GROUNDING ELECTRODE CONDUCTORS (MUST BE CONTINOUS AND CLAMPED TO GROUND RODS) 2) NEED WAIVER TO USE OVERHEAD ELECTRIC SERVICE |
|
| 06/01/2006 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO PRIOR INSPECTION REPORT ON SITE 2) PLAN CALLS FOR UNDERGROUND ELECTRIC SERVICE. YOU MUST OBTAIN A WAIVER TO USE OVER HEAD ELECTRIC SERVICE 3) PROVIDE PROOF THAT YOU HAVE TWO GROUND RODS AT LEAST 6 FEET APART-DIG UP RODS TO A DEPTH OF 8 INCHES OF ROD AND EXPOSE CONDUCTOR |
|
| 03/03/2006 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 02/22/2006 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* |