Permit: T05CM03900

Parcel: 107150580


Addresses:

2726 N GERONIMO AV

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
03/09/2006 FRAMING Approved IVRS - Inspection :*
03/03/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 1, 2, 4 AND 7 NOT DONE
2) SECURE WIRE TO MASTER BATH VENT FAN
02/22/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALL H2.5'S AT PATIO PER DETAIL 2/4
2) TERMINATE HOME RUNS IN MAIN SERVICE PANEL
3) BLOCK REGISTER BOOTS 3 SIDES
4) NAIL PROTECT VTR KITCHEN PONY WALL
5) BLOCK TUB WALLS
6) TERMINATE BATH ROMEX INTO EXHAUST FANS AND LAUNDRY
7) FIRE BLOCK ARCHWAY
02/13/2006 FRAMING Cancelled CANCELLED PER OWNER VERONICA #551-0628
02/13/2006 FRAMING Not ready for Inspection IVRS - Inspection :*