Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
06/17/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
05/30/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ALL METAL BOXES MUST BE GROUNDED
2) BOXES MUST EXTEND TO SURFACE OF SHEETROCK
3) ADD NAIL STOPS NORTH WALL
4) USE ROMEX CONNECTORS IN CEILING BOXES. FILL UNUSED HOLES IN CEILING BOXES WITH BLANKS
5) SECURE WIRES WITHIN 8" OF BOXES