Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/15/2005 | BUILDING ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 12/01/2005 | BUILDING ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* YOU MAY NOT USE CEILING GRID WIRES FOR ANYTHING EXCEPT GRID. THAT MEANS NO DATA CABLES, ELECTRIC CABLES ETC. INSTALL INSULATION AND PROPERLY SUPPORT IT AROUND DUCT PENETRATIONS THRU ROOF. YOU NEED SAFETY WIRES ON TRACK LIGHT |
|
| 11/21/2005 | BUILDING ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :*YOU NEED TO HAVE ALL CEILING GRID, DUCTING, WIRING AND SPRINKLERS COMPLETE BEFORE CALLING THIS INSPECTION WHERE IS YOUR REFLECTED CEILING PLAN |
|
| 11/03/2005 | BUILDING ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* |