Permit: T05CM03882

Parcel: 124081520


Addresses:

1312 E 8TH ST #01


Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T05CM03882

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
09/05/2006 MECHANICAL - INTERMEDIATE Approved
02/27/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
BOTH VERIFY DEPTH OF FAN COIL RAISED PLENIUMS VERY NARROW.
1. EAST SIDE APT. DRYER DUCT, NARROWED DOWN AT UPPER PLATE, TOP OF PORTION. THIS NEEDS TO BE OPENED UP TO CORRECT DIAMETER.
2. CAN'T TERMINATE CONDENSATE DRAIN INTO KITCHEN WASTE. ONLY BATHROOM LEV. WATE IS ACCEPTABLE
3. STILL NEED REVISED PLAN.
02/27/2006 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
02/07/2006 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
JOB AS INSTALLED DOES NOT REFLECT APPROVED SET OF PLANS.