Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05CM03882
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/05/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
08/24/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* UNIT #1 1. PROVIDE DEDICATED CKT TO MICROWAVE (1800 WATT) 2. RE-DO PANEL SCHEDULE SO IT IS LEGIBLE/NEAT UNIT #2 1. PROVIDE DEDICATED MICRO CKT 2. NEED COVER FOR MICRO RECEPT 3. DISHWASHER RECEPT BOX IS LOOSE 4. ONLY ONE NEUTRAL ALLOWED UNDER SAME SCREW IN PANEL. 5. ONLY SAME SIZE EQUIPMENT GROUNDS UNDER SAME SCREW IN PANEL. |
|
08/15/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* INSPECTION FOR UNIT ONE & EXTERIOR UNIT TWO OCCUPIED -- CHECK FOR SAME CORRECTIONS 1. NEED REAR EXTERIOR GFI FOR UNIT 1 2. HAVE INCORRECT FUSE SIZE IN AC DISCONNECTS ALOS, IDENTIFY UNIT ON EACH. DISC. 3. SMOKE DETECTORS IN BEDROOMS REQUIRE ARC FAULT PROTECTION. 4. PANEL DIRECTORY NOT CORRECTLY IDENTIFIED. 5. MICRO RECEPTACLE ENCLOSURE IS LOOSE 6. TIGHTEN ALL LOOSE DEVICES 7. A.C CONDENSATE PUMP TO BE USED AS LISTED -- PLUG IN 8. ANTI-TIP DEVICE FOR RANGE NOT HOLDING 9. STRAP FLEX FOR AIR HANDLER DISC. |