Permit: T05CM03882

Parcel: 124081520


Addresses:

1312 E 8TH ST #01


Inspection Status: Approved

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Permit Number - T05CM03882

Inspection Description - EXCAVATION/LAYOUT REBAR & ZON

Inspection Status - Approved

Date Description Inspector Results Comments
11/02/2005 EXCAVATION/LAYOUT REBAR & ZON Approved IVRS - Inspection :*
1. 4" SDR 35 SEWER FROM TAP AT MAIN TO 4" ABS CONNECTION AT UPPER CLEAN OUT OK.
2. ABS SEWER TO 2-WAY CLEAN OUTS OK
WATER TEST OK.
3. FELT TIP PENNED CHANGES DO NOT AN APPROVED PLAN MAKE. PLAN IS INCOMPLETE. NO SIZES, NO MAT'L TYPE, NO FINAL DESTINATION, ETC.
4. WATER CHANGES ARE THE SAME
INSTALLED IS 2-1 1/4" PVC PIPE.
5. HAVE WILDAN FINISH THEIR PLAN AND HAVE AVAILABLE AT NEXT INSPECTION.
6. HAVE 03040 YARDWATER ADDED TO PERMIT.