Permit: T05CM03875

Parcel: 131050030


Addresses:

5466 E 29TH ST

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
09/22/2005 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
1) PROVIDE AN AMERIVENT CAP ON WATER HEATER VENT. WILL CHECK ON FINAL
09/20/2005 MECHANICAL - INTERMEDIATE Cancelled IVRS - RI canceled
09/09/2005 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE HIGH AND LOW COMBUSTION AIR VENTS THRU THE ROOF AS PER PLANS
2) ALSO PROVIDE A MINIMUM 1" CLEARANCE FROM ROOF SHEATHING WHERE WATER HEATER VENT PENETRATE THE ROOF. REPAIR THE JOINT IN THE B VENT COMING APART. PROVIDE MINIMUM 3 SCREWS IN ALL JOINTS OF VENT CONNECTOR. PROVIDE ACCESS TO ROOF