Permit: T05CM03844

Parcel: 12709011M

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05CM03844

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/18/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/14/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*OK ROOF. BOXES MORE THAN 1/4" FROM BOX TO SURFACE TO USE APPROVED EXTENDER RUGS 214.20
BOND CABLE TRAY
INSTA HOT TO USE A DISCONNECTING MEANS
CORRECTLY ID GROUND & 130 GROUND CONDUCTOR
USE MANUFACTURERS HOLD DOWN CLIP FOR BACK FEED BREAKER.
CANNOT STACK LUGS AND ATTACH TO TRANSFORMER CASE 250.8, 250.12, 110.3
MANUFACTURERS INSTARUCTIONS FOR E. MON METERS REQUIRE.
TO BE ATTACHED TO A BREAKERS
WAITING ON UPS
PROVIDE LETTER FOR RELOCATION ??? METER TO 6TH FLOOR FOR PANEL 6"PC"
FINISH ITEM FROM PROVIOUS INSPECTIONS.