Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05CM03844
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/18/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
10/14/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*OK ROOF. BOXES MORE THAN 1/4" FROM BOX TO SURFACE TO USE APPROVED EXTENDER RUGS 214.20 BOND CABLE TRAY INSTA HOT TO USE A DISCONNECTING MEANS CORRECTLY ID GROUND & 130 GROUND CONDUCTOR USE MANUFACTURERS HOLD DOWN CLIP FOR BACK FEED BREAKER. CANNOT STACK LUGS AND ATTACH TO TRANSFORMER CASE 250.8, 250.12, 110.3 MANUFACTURERS INSTARUCTIONS FOR E. MON METERS REQUIRE. TO BE ATTACHED TO A BREAKERS WAITING ON UPS PROVIDE LETTER FOR RELOCATION ??? METER TO 6TH FLOOR FOR PANEL 6"PC" FINISH ITEM FROM PROVIOUS INSPECTIONS. |