Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
07/12/2006 PLUMBING - GAS PRESSURE TEST Approved
04/11/2006 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
GAS SYSTEM PRESSURE IS HOLDING STEADY.
WAITING ON PLAN REVISION FOR FINAL INSPECTION.
04/07/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
5 1/2 PSI ON GAS PIPING SYSTEM
PLAN SHOWS 2" GAS PIPING WITH BRANCH LINES TO HEATERS.
A 3" GAS LINE WITH A 2 1/2" BRANCH THAT IS CAPPED IN CEILING, HAS BEEN INSTALLED.
THE PIPING AND THE PLAN MUST LOOK ALIKE.
SEE NOTES FROM PREVIOUS INSPECTION.
03/17/2006 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
5 PSI ON 3" GAS LINE
THERE IS A LARGE VOLUME OF AIR IN A 8" GAS LINE
THIS WILL REQUIRE A 24 HR. TEST. PLEASE AIR UP GAS LINE
THE DAY BEFORE TEST. 94 UPC REQUIRES 10 PSI
PIPING NOT INSTALLED PER PLAN. REVISE PLAN.
3/4" GAS LINE IN WALL OK TO COVER IF PLAN IS REVISED AND PRESSURE IS HOLDING.