Permit: T05CM03834

Parcel: 140552990

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
08/15/2006 BUILDING - FINAL Approved IVRS - Inspection :*
08/10/2006 BUILDING - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspection
House occupied without approval
Remove all personal property from house
You must pay reinspection fee
08/04/2006 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE CITY OF TUCSON APPROVED SUBMITTAL FOR OUTSIDE LIGHTS
2) DBL LUGGING OF NEUTRAL AND GROUND WIRES NOT ALLOWED
3) HAND RAIL MUST BE 36" PLUS OR MINUS 2" ABOVE STAIR BULL NOSE PLANE
4) PENINSULA REQUIRES GFCI OUTLET
5) WRONG FAU GAS PACK NOT ALLOWED ON ALL ELECTRIC HOUSE
6) INSTALL ROOF JACKS ON LOW VOLTAGE AND CONDENSATE ROOF PENETRATIONS