Permit: T05CM03833

Parcel: 140553070

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
04/21/2006 FRAMING Approved IVRS - Inspection :*
03/27/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) LOOSE #12 ROMEX 2ND FLOOR (ROOF RECEPTACLE) ?
2) NEED DWV TEST
3) VENT FOR TUB TO BE 6" ABOVE FLOOD RIM BEFORE GOING VERT
4) SUPPORT DROP CEILING AT TOP OF STAIR 2ND FLOOR
5) OVER SPAN 2ND FLOOR TUBS TWO
6) #8 FOR ROOF UNIT
7) BANG PLATE CONDENSATE TOP PLATE 2ND FLOOR
8) BACKING AT TUB SIDE (NORTH TUB)
9) MISSING 5, HTT16 H.D.'S
10) MISSED #3 SHEAR AT FRONT ENTRY, #1 ABOVE #3 AT STAIR HTT 16 MISSING
11) NO DETAIL FOR PORCH POST 2ND FLOOR
03/20/2006 FRAMING Not ready for Inspection IVRS - Inspection :*
HOLES THRU OUT ON WATER BARRIER FOR STUCCO