Permit: T05CM03830

Parcel: 140378200


Addresses:

6787 S AQUILINE DR

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
12/01/2005 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
11/29/2005 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FRONT P-2 NOT NAILED AT 4" ON CENTER
2) SOUTH P-2 NOT NAILED PER PLAN
3) REAR P-1 NOT NAILED
4) NAIL TEMP BRACING 2-16D NAILS ON ENDS
5) OSB ROOF SHEATHING MUST BE INSTALLED WITH GRAIN ACROSS TRUSSES FRONT ENTRY. BLOCK OK TO DRY ROOF
11/23/2005 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) COMPLETE SHEAR NAILING
2) STRAP TO REPLACE CABIN TIE SOUTH WEST CORNER
3) REPLACE STRAP TO 2ND FLOOR BY S.G.D.
4) BLOCK AND SHEET BETWEEN TRUSSES UNDER KNOCKOUT OVER FRONT PATIO PER S-2
5) STOPPED INSPECTION