Permit: T05CM03812

Parcel: 12513020C


Addresses:

3113 E 1ST ST #105

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
04/11/2006 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
04/07/2006 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. YOU HAVE OVERFILLED BOXES -- CHECK ALL OF THEM
2. INSTALL K.O BLANKS AS NEEDED.
3. MAKE SURE ALL FIXTURES HAVE SLACK WIRES AND THEY ARE EFFECTIVE.
01/31/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*60 THOUGH AND TIGHTEN ALL CONNECTIONS TO ALL SET SCREWS AND BUSHINGS BEFORE TEP ARRIVES