Permit: T05CM03807

Parcel: 13316037H

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
02/01/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
RECEIVED LETTER FOR "512" CABLE
1. LABEL DISCONNECTS
2. MAINTAIN WORKING CLEARANCE IN FRONT OF DISCONNECT
3. SUPPORT SEAL TITE UP OFF OF ROOF
11/14/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK ROUGH ELECTRIC SUBJECT TO LETTER FOR SE CABLES
11/10/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PLEASE ADD SUITE# TO PERMIT
2. SUPPORT SECOND SIDE OF PANEL
3. SUPPORT NM CABLES ABOVE PANEL - A BOARD AND STAPLES ARE NEEDED.
4. HAVE ARCHITECT AUTHORIZE USE OF "SE" CABLE FOR FEEDER.