Permit: T05CM03779
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/14/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/09/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. PLEASE FINISH ITEMS #1 & 2 |
|
| 02/07/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) PLANS FOR PAGE E-3 CALL FOR 2 CIRCUITS TO RECEPTACLES. ISOTROL PANEL THAT BREAKERS THE GROUNDED CONDUCTOR WITH ONLY ONE CIRCUIT TO EACH RECEPTACLE. PLEASE REVISE PLANS TO SHOW REFLECTED WORK 2) PLEASE VERIFY LISTING FOR CHEMETRON UNIT MED GAS AND VACUUM PUMP SYSTEM 3) SUPPORT FLEX CONDUITS AND BOXES FOR FIRE ALARM 4) WEATHER PROOF COVERS TO BE WEATHER PROOF WHETHER OR NOT PLUGED INTO 406.8 5) BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING 7) TIGHTEN LOOSE FITTINGS AT A/C CONTROL PANEL |