Permit: T05CM03778

Parcel: 133243690


Addresses:

100 N PANTANO RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/14/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/13/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING 314.20
2. USE ALC AND APPROVED HARDWARE FOR DEVICES
3. HAND DRYER CONDUCTOR NOT IN BOX BUT EXPOSED TO DRYWALL.
02/27/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELLED
02/16/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
02/24/2006 ELECTRIC - FINAL Partial Approval CHANGED TO PARTIAL SO CONTRACTOR CAN FINISH ADA BATHROOMS