Permit: T05CM03766

Parcel: 141153550

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T05CM03766

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/30/2006 BUILDING - FINAL Approved IVRS - Inspection :*
01/27/2006 BUILDING - FINAL Partial Approval IVRS - Inspection :*
I CANNOT PERFORM INSPECTIONS IN ILLEGALLY OCCUPIED SPACES
1. YOU MUST POST A BAND FOR T.C.O
2. OK TCO
3. PROVIDE #6 & #7 ABOVE
12/30/2005 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SHELL MUST BE FINALED BEFORE TI FINALED
2. SIGN AT ENTRANCE "DOOR TO REMAIN UNLOCKED..."
3. FINISH ALL WORK
4. 27" MIN. KNEE CLEARANCE IN W.L. UNDER LAVATORY REQUIRED
5. YOU HAVE SHRUNK DIMENSION OF RESTROOM 4 WHICH AS RESULTED IN IMPROPER CLEARANCE @ DOOR (18" SIDE CLEARANCE REQUIRED LATCH SIDE OF JAMB PER ANSI 117.1)
6. ALL ACCESSIBILITY SIGNAGE MUST BE IN PLACE INCLUDING PARKING.
7. PROVIDE APPROVED FINALS FROM OTHER TRADES.