Permit: T05CM03759

Parcel: 10511061R

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05CM03759

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/20/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/19/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) CORD NOT ALLOWED FOR PERMANENT WIRING
2) USE APPROVED FILLER BLANKS
09/18/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING 314.20 METAL NOT APPROVED
2) GROUND JUNCTION BOXES 4-D IDENTIFY ISOLATED GROUNDS
3) WATER HEATER NOT TO BE CORD AND PLUG
ALSO A DISCONNECTING MEANS
4) FILL UNUSED OPENING IN PANEL
09/15/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*